what is mm2 in cable and how cable filing is done in cable tray?

1️⃣ What is mm² in cable?

mm² = Square millimeter
It tells the cross-sectional area of the copper conductor inside the cable — not the outer diameter.

🔹Example:

  • 2.5 mm² cable means the copper area is 2.5 mm²
  • 4 mm² cable → copper area is 4 mm²
    (Bigger mm² = more current flow)

🌟 2️⃣ Why mm²? (Not diameter)

Because some cables are:

  • Round
  • Stranded (many small wires)
  • Shaped differently

So area is fixed… but diameter changes depends on insulation thickness.


🌟 3️⃣ How to calculate diameter from mm²?

Assume the conductor is round:

📌 Formula:

Diameter=4×Areaπ\text{Diameter} = \sqrt{\frac{4 \times \text{Area}}{\pi}}Diameter=π4×Area​​


Example: 2.5 mm² cable

Diameter=4×2.53.14=3.18=1.78mm\text{Diameter} = \sqrt{\frac{4 \times 2.5}{3.14}} = \sqrt{3.18} = 1.78\,\text{mm}Diameter=3.144×2.5​​=3.18​=1.78mm

But this is just copper
Actual cable outer diameter ≠ this number
Because we must add:

✔ Insulation thickness
✔ Inner/Outer sheath (for multi-core)

So outer diameter is usually:

Cable SizeApprox Outer Diameter
1.5 mm²~3.3 – 3.7 mm
2.5 mm²~4.2 – 5.0 mm
4 mm²~4.9 – 6.0 mm
6 mm²~5.5 – 7.0 mm

(Different brands ⇒ slightly different sizes)


🌟 4️⃣ Cable Tray Filling

Tray filling rule (common):

✔ Only 40% of tray area can be filled with cables

Steps:
1️⃣ Get cable outer diameter
2️⃣ Area of one cable:A=π(D2)2A = \pi \left(\frac{D}{2}\right)^2A=π(2D​)2

3️⃣ Tray usable area:Ausable=Tray width×height×0.4A_{\text{usable}} = \text{Tray width} \times \text{height} \times 0.4Ausable​=Tray width×height×0.4

4️⃣ Total cables allowed:N=AusableAcableN = \frac{A_{\text{usable}}}{A_{\text{cable}}}N=Acable​Ausable​​


🔹 Small Example:

Tray: 200 mm width x 50 mm height
Usable area = 200 × 50 × 0.4 = 4000 mm²

Cable OD: 8 mm → area:A=3.14×42=50.24mm2A = 3.14 \times 4^2 = 50.24\,\text{mm}^2A=3.14×42=50.24mm2

Number of cables:4000/50.2479 cables4000 / 50.24 ≈ 79 \text{ cables}4000/50.24≈79 cables


✅ Summary You Can Remember

TermMeaning
mm²Area of copper conductor
DiameterComes from thickness of insulation, varies by brand
Tray fillMax 40% area

If you want — I can create an Excel sheet for you:
✔ You enter tray size + cable OD → It calculates number of cables

Would you like the Excel?
And tell me your commonly used cable sizes! 😊

sample calculation

Sure! Here is one complete sample calculation step-by-step 👇
(You can save this as your reference)


📌 Sample Cable Tray Fill Calculation

🔹 Given:

ParameterValue
Tray Width300 mm
Tray Height50 mm
Cable Type4 mm² single core
Cable Outer Diameter6.0 mm
Allowable Fill40% of Tray Area

✏ Step-1: Find Tray Usable Area

Tray Total AreaAtray=300×50=15000 mm2A_{tray} = 300 \times 50 = 15000\ mm^2Atray​=300×50=15000 mm2

Usable Area (40%)Ausable=15000×0.4=6000 mm2A_{usable} = 15000 \times 0.4 = 6000\ mm^2Ausable​=15000×0.4=6000 mm2


✏ Step-2: Area of One Cable

Outer Diameter = 6 mm
Radius = D/2 = 3 mmAcable=π×r2=3.14×32A_{cable} = \pi \times r^2 = 3.14 \times 3^2Acable​=π×r2=3.14×32Acable=3.14×9=28.26 mm2A_{cable} = 3.14 \times 9 = 28.26\ mm^2Acable​=3.14×9=28.26 mm2


✏ Step-3: Number of Cables Allowed

N=AusableAcable=600028.26=212.3N = \frac{A_{usable}}{A_{cable}} = \frac{6000}{28.26} = 212.3N=Acable​Ausable​​=28.266000​=212.3


🎯 Final Answer

✔ Maximum cables allowed in tray:212 cables\approx \boxed{212\ cables}≈212 cables​


🔍 Quick Summary Table

DescriptionValue
Tray usable area6000 mm²
Cable area28.26 mm²
Cables allowed≈ 212 nos